Operating voltage |
|
LSN part |
15 V DC to 33 V DC |
Other expansion module functions |
9 V DC to 30 V DC |
Current consumption |
|
LSN part |
4.95 mA |
Other expansion module functions |
- Max. 370 mA at + 12 V- Max. 180 mA at + 28 V |
Primary lines PL 1 – PL 6 |
|
Connection options |
6 detector zones can be programmed as hold-up, intrusion, tamper, closure, or entry |
Terminal resistance |
RE = 12.1 kilohm |
Interruption voltage |
Approx. 6 V |
Line resistance |
Max. 100 Ohm |
Alarm criteria |
± 40% of terminal resistance |
Response time |
< 200 ms |
Control outputs S1 - S3 |
|
Principle |
Open collector, 12 V when active0 V switching |